PID
3047219

Battery Monitoring System

share

Request For Quotation
The BQMS Battery Monitoring System is a modular system that allows for complete monitoring of a single or multiple battery systems.
Certification
Award
Shipping
  • Modes of Transport EXW
Payment

140+ Global Payments, trusted and secure payment provided by PayVerse.

Learn More
Quantity
MOQ : 1 Sets

Detailed Description

 

 

 

 

 

 

 

[Company Introduction]

 

Introduction of WATON

 

Waton Inc, specialized in emergency power technologies, has grown up under the philosophy of “best services to the customers”, according to the development of Korean industrial field in power supplies and battery diagnosis since its creation in 1984.


Now, Waton provides you total solutions of environment-friendly power supplies and battery diagnostic apparatuses that meet all needs of customers interested in emergency power supply systems, and is driving innovation in renewal power monitoring technology for next-generation.

Presently, we are manufacturing IBEX-Series named as a Portable Battery Quality Tester and IBwatch named as Battery Monitoring System. Major customers are telecom & utility companies, industrials, battery and UPS manufacturers.
We export our BMS to USA, China, Turkey, England, Thailand, Malaysia, Mexico, Indonesia and others.

 


Thank you.

 

 

 

[ Product Description ]

 

 The BQMS Battery Monitoring System is a modular system that allows for complete monitoring of a single or multiple battery systems. Parameters monitored include string voltage, DC current, cell voltage, cell / connection resistance, cell temperature, & ambient temperature. The BQMS is designed for use on vented lead acid, valve regulated lead acid, and nickel-cadmium battery systems.

 

 The included Centroid Snet2 Battery Management Software allows for remote viewing and data management. Report generation, trending analysis, & detailed alarming can all be viewed on a single or multiple PC’s on the same network as the BQMS. Alternatively, the BQMS can be configured to communicate via Modbus to a building management system, SCADA, or other custom fit management system.

All BQMS systems have the option to include up to (8) drycontact relays for additional external device alarming.

 

 

 

[ Product Description ]

 

Technical Specifications

Measurement Range:

Jar/Cell Voltage: 0.0 – 16.0 VDC

Jar/Cell Temperature: -20 – 80°C (-4 – 176°F)

DC Voltage: -1000 – 1000V

DC Current: 999.9 VDC / 999.9 A

Accuracy:

DC Voltage / Current: ±0.5% / ±1%

Temperature: ±2%

Internal Resistance: ±2%

Cell Voltage: ±0.5%

Resolution:

DC Voltage / Current: 0.1 V / 0.1 A

Cell Voltage: 0.001 V

Internal Resistance: 0.001 mΩ

Temperature: 0.1°C

Test Speed / Test Load:

30/seconds per bank

Measuring Interval:

Adjustable from 10 min to 160 hours (voltage & I.R.)

Data Transfer:

TCP/IP, Modbus, SNMP & others

Alarm Relays

Up to 8 optional Form C relays

Operating Environment:

Temperature: 0 – 65 °C (32 – 150 °F)

Relative Humidity: Under 80%

Power Requirements:(1)

CCU: 48V (36 – 72 VDC) / 125V (120 –370 VDC)

Module: 2V (26 – 18 VDC) / 12V (18 –36 VDC)

Power Consumption:

CCU: under 3W

Module: under 10W

Dimensions:

L x D x H

CCU: 210 x 76 x 200 mm (8.25 x 3 x 7.9 in)

Module: 114 x 70 x 39 mm (4.5 x 2.75 x 1.5 in)

 

 

 

 